Configuration, Code table – Lenze EVF9333−xV User Manual
Page 385

Configuration
Code table
8.5
l
8.5−37
EDSVF9333V EN 4.0−11/2007
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0594 MONIT SD6
3
0
TRIP
Activation of the motor
temperature monitoring with KTY
at X8
l
Use C0594 = 0 or 2 to activate
monitoring
l
In case of a short circuit or
interruption at X8/5 and X8/8
the fault message SD6 is
activated
l
Configuration of the response
when exceeding the motor
temperature
– Fixed operating temperature
in C0583
– Variable operating
temperature in C0584
^
6.6−10
See System
Manual
(extension)
2
Warning
3
Off
C0595 MONIT CE4
3
0
TRIP
Configuration of monitoring CE4,
BUS−OFF (system bus)
See System
Manual
(extension)
2
Warning
3
Off
C0596 NMAX limit
4000 0
{1 rpm}
36000 Configuration of monitoring N
max
,
maximum system speed exceeded
See System
Manual
(extension)
C0597 MONIT LP1
3
0
TRIP
Configuration of monitoring the
motor phases LP1
See System
Manual
(extension)
2
Warning
3
Off
C0598 MONIT SD5
3
0
TRIP
Configuration of monitoring SD5,
open circuit at analog input X6/1,
X6/2
See System
Manual
(extension)
2
Warning
3
Off
C0599 Limit LP1
5.0
1.0
{0.1 %}
10.0 Configuration of current limit LP1,
current limit value for monitoring
the motor phases in C0597
See System
Manual
(extension)
C0600 Function
1
0
OUT = IN1
Function selection, function block
ARIT2
See System
Manual
(extension)
1
OUT = IN1 + IN2
2
OUT = IN1 − IN2
3
OUT = IN1 * IN2
4
OUT = IN1 / IN2
5
OUT = IN1 / (100 − IN2)
C0601
s
^ Selection list 1
Configuration of analog input
signal, function block ARIT2
1 CFG: IN
1000 FIXED0%
ARIT2−IN1
2 CFG: IN
1000 FIXED0%
ARIT2−IN2
C0602
−199.99
{0.01 %}
199.99 Function block ARIT2
l
Display of the signals linked in
C0601
1 DIS: IN
ARIT2−IN1
2 DIS: IN
ARIT2−IN2