Technical data
General data and operating conditions
3.1
l
3.1−2
EDSVF9333V EN 6.2−04/2012
Ambient conditions
Site altitude
< 4000 m amsl
> 1000 m amsl: reduce the rated output current by
5 %/ 1000 m.
Mechanical
Vibration resistance
(9.81 m/s
2
= 1 g)
Germanischer
Lloyd 5 ... 13.2 Hz
Amplitude ±1 mm 13.2 ... 100 Hz:
acceleration resistant up to 0.7 g
IEC/EN 60068−2−6
10 ... 57 Hz
Amplitude 0.075 mm 57 ... 150 Hz:
acceleration resistant up to 1 g
Electrical
AC−mains
connection
Max. mains
voltage range
320 V − 0 % ... 528 V + 0 %
Mains frequency
45 Hz − 0 % ... 65 Hz + 0 %
Power system TT,
TN
Operation permitted without restrictions with
earthed neutral.
Power system IT
Operation only permitted with the device variants
V024 or V100.
Operation permitted without restrictions with
insulated neutral.
Observe instructions on specific measures!
Operation on
public supply
systems
EN 61000−3−2
Limitation of harmonic currents
Total output at the
mains
Compliance with the
requirements
1)
< 1 kW
With mains choke.
> 1 kW
Without additional
measures.
1)
The additional measures mentioned have the effect that solely
the controllers meet the requirements of EN 61000−3−2. The
machine/system manufacturer is responsible for the compliance
with the requirements for the machine/system!
DC−mains
connection
Max. mains
voltage range
450 V − 0 % ... 740 V + 0 %
Operating
conditions
DC voltage must be symmetrical to PE.
The controller will be destroyed when +U
G
or −U
G
are earthed.
Motor connection
Length of the
motor cable
< 50 m
shielded
< 100 m
unshielded
At rated mains voltage and a switching frequency
of
£ 8 kHz without additional output filter.
For compliance with EMC regulations, the
permissible cable length might change.
Mounting conditions
Mounting place
In the control cabinet
Mounting position
Vertical
Free spaces
Dimensions
Weights
^ 4−1