Commissioning – Lenze EVF9333−xV User Manual
Page 197

Commissioning
Adjusting the motor
Motor temperature monitoring with PTC or thermal contact
6.6
6.6.3
l
6.6−9
EDSVF9333V EN 6.2−04/2012
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze Selection
C0585 MONIT OH8
3
0
TRIP
Configuration of motor
temperature monitoring
l
Temperature monitoring via
PTC input (T1, T2)
^
6.6−8
See System
Manual
(extension)
2
Warning
3
Off
)
Note!
ƒ
In the Lenze setting the motor temperature monitoring is
switched off!
ƒ
If you work with several parameter sets, the monitoring must
be activated separately in each parameter set!
1. Connect the monitoring circuit of the motor to T1 and T2.
– With 1.6 k
W < R < 4 kW, the monitoring responds.
2. Set the controller reaction:
– C0585 = 3: Temperature monitoring of the motor is switched off.
– C0585 = 0: TRIP error message (display of keypad: OH8
a)
– C0585 = 2: Warning signal (display of keypad: OH8
e)
Connect the PTC input with a fixed resistor:
ƒ R > 4 k
W: The fault message OH8 must be activated.
ƒ R < 1 k
W: Fault message must not be activated.
Activation
Function test