Configuration – Lenze EVF9333−xV User Manual
Page 334

Configuration
Function blocks
Internal motor control with vector control (MCTRL2)
8.2
8.2.7
l
8.2−72
EDSVF9333V EN 6.2−04/2012
When the speed falls below a settable speed setpoint threshold, the function
"DC injection braking" is activated.
)
Note!
Automatic DC−injection braking has priority over quick stop.
Special features of vector control with feedback
ƒ If the DC braking current (C0036)
£ than the motor magnetising current,
the motor magnetising current is injected.
ƒ If the DC braking current (C0036)
> than the motor magnetising current,
the DC braking current is injected.
Setting
Selection
Code
Description
DC braking current
C0036
DC braking current with which the motor is braked
Speed setpoint threshold
C0019
If the values fall below the threshold, DC−injection
braking is released
Hold time
C0107
Duration of DC−injection braking. After the hold time,
pulse inhibit is set.
(
Stop!
An excessive DC braking current and braking time can thermally
overload the motor. Special care must be taken when using
self−ventilated motors.
Automatic DC injection
braking