Configuration – Lenze EVF9333−xV User Manual
Page 329

Configuration
Function blocks
Internal motor control with vector control (MCTRL2)
8.2
8.2.7
l
8.2−67
EDSVF9333V EN 6.2−04/2012
Flying restart circuit with protection against unexpected start−up
(C0142 = 2):
0
1
2
3
4
9300vec087
Fig. 8.2−23
Signal characteristic for manual start with flying restart circuit (C0142 = 2)
0 Speed setpoint (e.g. AIN−OUT)
1 Actual speed value
2 Fault (e.g. DCTRL−FAIL = HIGH)
3 Pulse inhibit (e.g. DCTRL−IMP = HIGH)
4 Enable controller (e.g. X5/28 = HIGH)
The motor rotates with setpoint
A fault (e.g. mains failure, TRIP SET) activates a pulse inhibit c . The motor
coasts. After eliminating the fault (e.g. mains recovery, TRIP RESET) the pulse
inhibit remains active until the controller is enabled again (e.g. LOW−HIGH
edge at X5/28)
Important in case of an OU message: if the OU message is not pending
anymore, the pulse inhibit is deactivated.
The flying restart circuit is active now and determines the current motor
speed
The motor is accelerated along the set acceleration ramp to the speed
setpoint and is being kept there