Configuration, Code table – Lenze EVF9333−xV User Manual
Page 364

Configuration
Code table
8.5
l
8.5−16
EDSVF9333V EN 4.0−11/2007
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0149
s
Auto ident
0
0
Id
inactive
Automatic identification is
inactive
Automatic motor data
identification
1. Inhibit controller, wait until
drive has stopped
2. Enter the correct values of the
motor nameplate into C0087,
C0088, C0089, C0090, C0091
3. Set C0149 = 1, confirm with
v
4. Enable controller
The identification
– starts,
c goes off. The
motor "whistles" but does
not rotate!
– lasts approx. 1 ... 2 min
– is completed when
c is lit
again
5. Inhibit controller:
^
6.6−14
1
Id active Automatic identification is
active
l
The identification starts
automatically after
controller enable
l
After a faulty
identification, the process
is restarted after TRIP
RESET or mains switching
and subsequent
controller enable
C0150 Status word
Bit00
—
Bit08
Status code
Read only
Decimal status word for
networking via automation
interface (AIF)
l
Binary interpretation indicates
the bit states
See System
Manual
(extension)
Bit01
IMP
Bit09
Status code
Bit02
—
Bit10
Status code
Bit03
—
Bit11
Status code
Bit04
—
Bit12
Warning
Bit05
—
Bit13
Message
Bit06
n = 0
Bit14
—
Bit07
CINH
Bit15
—
C0151 DIS: FDO (DW)
Read only
l
Free digital outputs (FDO)
l
Hexadecimal representation of
the digital output signals
configured in C0116
l
Binary interpretation indicates
the bit states
See System
Manual
(extension)
C0155 Status word 2
Bit00
Fail
Bit08
R/L
Display only
l
Binary interpretation indicates
the bit states
Bit01
M
max
Bit09
—
Bit02
I
max
Bit10
—
Bit03
IMP
Bit11
—
Bit04
RDY
Bit12
—
Bit05
CINH
Bit13
—
Bit06
TRIP
Bit14
—
Bit07
Init
Bit15
—