Configuration, Code table – Lenze EVF9333−xV User Manual
Page 360

Configuration
Code table
8.5
l
8.5−12
EDSVF9333V EN 4.0−11/2007
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0116
s
^ Selection list 2
Configuration of free digital
outputs (FDO)
l
Signals can only be evaluated
when being networked with
automation interfaced
See System
Manual
(extension)
1 CFG: FDO−0
1000 FIXED0
... ...
...
...
32 CFG: FDO−31
1000 FIXED0
C0117
s
^ Selection list 2
Configuration of digital inputs
signals, function block DIGOUT
A change of the basic
configuration in C0005 changes
the signal assignment!
^ 6.5−3
See System
Manual
(extension)
1 CFG: DIGOUT1
15000 DCTRL−TRIP
Terminal X5/A1
2 CFG: DIGOUT2
10650 CMP1−OUT
Terminal X5/A2
3 CFG: DIGOUT3
500
DCTRL−RDY
Terminal X5/A3
4 CFG: DIGOUT4
5003 MCTRL−MMAX
Terminal X5/A4
C0118
0
High active
HIGH level is
active
Inversion of digital output signals,
function block DIGOUT
1
LOW active
LOW level is active
1 DIGOUT1 pol
1
Terminal X5/A1
2 DIGOUT2 pol
1
Terminal X5/A2
3 DIGOUT3 pol
0
Terminal X5/A3
4 DIGOUT4 pol
0
Terminal X5/A4
C0120 OC6 LIMIT
0
00
{1 °C}
120 Threshold for I
2
× t monitoring
(motor).
l
0 = I
2
× t monitoring
switched−off
l
I
2
× t > C0120
ð trip OC6
C0121 OH7 limit
150
45
{1 °C}
150 Setting of the operating
temperature for monitoring OH7
l
Only for KTY at X8
l
Monitoring OH7 is configured
in C0584
^
6.6−10
See System
Manual
(extension)
C0122 OH4 limit
80
45
{1 °C}
85 Configuration of monitoring OH4
l
Monitoring of the heatsink
temperature
l
Activating monitoring with
C0582
l
Temperature in C0122 reached:
– Warning OH4 is initiated
See System
Manual
(extension)
C0125 Baudrate
0
0
9600 baud
LECOM baud rate
l
Baud rate for accessory module
2102
1
4800 baud
2
2400 baud
3
1200 baud
4
19200 baud
C0126 MONIT CE0
3
0
TRIP
Configuration of monitoring CE0
l
Error message in case of
communication error AIF
See System
Manual
(extension)
2
Warning
3
Off
C0127 OC8 LIMIT
0
0
{1 °C}
120 Threshold for I
2
× t advance
warning (motor).
l
0 = I
2
× t advance warning
switched−off
l
I
2
× t > C0127
ð fault message
OC8 (response set in C606)
C0128 TAU MOTOR
5.0
0.1
{0.1 min}
50.0 Thermal time constant of the
motor
The time constant is required for
calculating the I
2
× t
disconnection.