Configuration, Code table – Lenze EVF9333−xV User Manual
Page 384

Configuration
Code table
8.5
l
8.5−36
EDSVF9333V EN 4.0−11/2007
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0581 MONIT EEr
0
0
TRIP
Configuration monitoring EEr,
external fault
See System
Manual
(extension)
1
Message
2
Warning
3
Off
C0582 MONIT OH4
2
2
Warning
Configuration monitoring OH4,
heatsink temperature
l
The operating temperature can
be set in C0122
See System
Manual
(extension)
3
Off
C0583 MONIT OH3
3
0
TRIP
Configuration of motor
temperature monitoring with
fixed operating temperature
l
Only for KTY at X8
l
The operating temperature is
fixed at 150 °C
^
6.6−10
See System
Manual
(extension)
2
Warning
3
Off
C0584 MONIT OH7
3
2
Warning
Configuration of monitoring
motor temperature with variable
operating temperature
l
Only for KTY at X8
l
When reaching the
temperature set in C0121 the
warning OH7 is activated
^
6.6−10
See System
Manual
(extension)
3
Off
C0585 MONIT OH8
3
0
TRIP
Configuration of motor
temperature monitoring
l
Temperature monitoring via
PTC input (T1, T2)
^ 6.6−8
See System
Manual
(extension)
2
Warning
3
Off
C0587 MONIT SD3
3
0
TRIP
Configuration of monitoring SD3,
encoder at X9
l
Monitors the voltage supply at
X9/pin 8
See System
Manual
(extension)
2
Warning
3
Off
C0588 MONIT
H10/H11
0
0
TRIP
Configuration of monitoring H10
and H11, thermal sensors in the
controller
l
H10: Sensor error − heatsink
temperature
l
H11: Sensor error − interior
temperature
See System
Manual
(extension)
3
Off
C0591 MONIT CE1
3
0
TRIP
Configuration of monitoring CE1,
communication error at CAN−IN1
See System
Manual
(extension)
2
Warning
3
Off
C0592 MONIT CE2
3
0
TRIP
Configuration of monitoring CE2,
communication error at CAN−IN2
2
Warning
3
Off
C0593 MONIT CE3
3
0
TRIP
Configuration of monitoring CE3,
communication error at CAN−IN3
2
Warning
3
Off