Adjusting the motor
Automatic collection of motor data
6.6
6.6.6
l
6.6−15
EDSVF9333V EN 6.2−04/2012
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze Selection
C0084
s
Mot Rs
à
0.00
{0.01 m
W}
100000.
00
Motor stator resistance
à
Value is determined by motor
parameter identification
(C0148, C0149)
^
6.6−1
^
6.6−14
C0087
s
Mot speed
à
50
{1 rpm}
36000 Rated motor speed
à
depending on C0086
l
Motor selection in C0086 set
the corresponding rated motor
speed in C0087
l
Change of C0087 sets
C0086 = 0
^
6.6−1
C0088
s
MOT CURRENT
à
0.5
{0.1 A}
500.0 Rated motor current
à
Depending on C0086
l
Selection of a motor in C0086
sets the corresponding rated
motor current in C0088
l
Change of C0088 sets
C0086 = 0
^
6.6−1
C0089
s
Mot frequency
à
10
{1 Hz}
5000 Rated motor frequency
à
depending on C0086
l
Motor selection in C0086 sets
the corresponding rated motor
frequency in C0089
l
Change of C0089 sets
C0086 = 0
^
6.6−1
C0090
s
Mot voltage
à
0
{1 V}
1000 Rated motor voltage
à
depending on C0086
l
Motor selection in C0086 sets
the corresponding rated motor
voltage in C0090
l
Change of C0090 sets C0086 =
0
^
6.6−1
C0091
s
Mot cos phi
à
0.50
{0.01 }
1.00 Motor cos
j
à
depending on C0086
l
Motor selection in C0086 sets
the corresponding motor cos
j
in C0091
l
Change of C0091 sets
C0086 = 0
^
6.6−1
C0092
s
Mot Ls
à
0.0
{0.1 mH}
6500.0 Motor stator inductance
à
Value is evaluated by motor
parameter identification from
C0088, C0089, C0090 and
C0091
à
Selection of a motor in C0086
sets the corresponding stator
inductance value in C0092
^
6.6−1