Configuration, Code table – Lenze EVF9333−xV User Manual
Page 366

Configuration
Code table
8.5
l
8.5−18
EDSVF9333V EN 4.0−11/2007
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0168
Display of the fault messages in
the history buffer
l
Keypad: LECOM error number
See System
Manual
(extension)
1 Fail no. act
Active fault
2 Fail no. old1
Last fault
3 Fail no. old2
Second to last fault
4 Fail no. old3
Third last fault
5 Fail no. old4
Fourth−last fault
6 Fail no. old5
Fifth−last fault
7 Fail no. old6
Sixth−last fault
8 Fail no. old7
Last but six fault
C0169
Display in [s]
Displays at what time the fault
(C0168) has occurred since mains
connection (C0179)
l
If a fault is followed by another
fault for several times, only the
time of the last occurrence is
stored
1 Failtime act
Active fault
2 Failtime old1
Last fault
3 Failtime old2
Second to last fault
4 Failtime old3
Third last fault
5 Failtime old4
Fourth−last fault
6 Failtime old5
Fifth−last fault
7 Failtime old6
Sixth−last fault
8 Failtime old7
Last but six fault
C0170
Displays how many times the
fault (C0168) has occurred after
the last mains connection
1 Counter act
Active fault
2 Counter old1
Last fault
3 Counter old2
Second to last fault
4 Counter old3
Third last fault
5 Counter old4
Fourth−last fault
6 Counter old5
Fifth−last fault
7 Counter old6
Sixth−last fault
8 Counter old7
Last but six fault
C0173
s
UG limit
1
Adaptation of UG thresholds
Check during commissioning and
adapt, if necessary!
All controllers in the system must
have the same threshold!
See System
Manual
(extension)
Mains
LU
OU
0
< 400 V
285 V
770 ... 755 V
Device with or without brake
chopper
1
400 V
285 V
770 ... 755 V
2
460 V
328 V
770 ... 755 V
3
480 V
342 V
770 ... 755 V
Device without brake chopper
4
480 V
342 V
800 ... 785 V
Device with brake chopper
C0178 Op timer
{s}
Display only
Total time of the controller enable
(X5/28 = HIGH)
C0179 mainstimer
{s}
Display only
Total time of mains "ON"