Configuration – Lenze EVF9333−xV User Manual
Page 289

Configuration
Function blocks
Internal motor control with V/f characteristic control (MCTRL1)
8.2
8.2.6
l
8.2−27
EDSVF9333V EN 6.2−04/2012
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0018 fchop
6
Switching frequency of the
inverter
l
General rule: the lower the
switching frequency the
– lower the power loss
– higher the noise generation
– better the concentricity
factor
– Observe derating
information at high
switching frequencies
l
The max. output frequency
(f
out
) amounts to:
– f
chop
= 16 kHz
Þf
out
= 600 Hz
– f
chop
= 8 kHz
Þf
out
= 300 Hz
– f
chop
= 4 kHz
Þf
out
= 150 Hz
– f
chop
= 2 kHz
Þf
out
= 150 Hz
^ 6.9−1
0
auto chop
automatic
change−over of the
switching
frequency
between
16/8/2 kHz
1
2 kHz sin
optimised smooth
running
2
4 kHz f_top
power−optimised
3
8 kHz f_top
power−optimised
4
8 kHz sin
noise optimised
5
16 kHz sin
noise optimised
6
auto 8/2 kHz
noise /
power−optimised
with automatic
change−over to
low switching
frequency
C0021 slipcomp
à
−20.00
{0.01 %}
20.00 Slip compensation
à
Change of C0086, C0087 or
C0089 sets C0021 to the
calculated rated slip of the
motor
l
When changing over to the
vector control mode, C0021 is
set to 0
^
6.11−1
^
8.2−25
^
8.2−48
C0022 IMAX CURRENT
à
0
{0.01 A}
− I
max
limit in motor mode
à
Depending on C0086
^
6.6−13
C0023 Imax gen.
à
0
{0.01 A}
− I
max
limit in generator mode
à
Depending on C0086
^
6.6−13
C0036 DC brk value
0.0
0.0
{0.1 A}
− Set DC braking current
à
depends on the controller
^
8.2−25
^
8.2−48
C0042 DIS: QSP
Quick stop
l
Display only
^
8.2−25
^
8.2−48
0
QSP inactive
Quick stop is not active
1
QSP active
Quick stop is active
C0050 MCTRL−NSET2
−100.00
{0.01 %}
100.00 Speed setpoint, function block
MCTRL
l
Display of the speed in [%] of
C0011
^
8.2−25
^
8.2−48
C0051 MCTRL−NACT
−36000
{1 rpm}
36000 Actual speed value, function block
MCTRL
l
Read only
^
8.2−25
^
8.2−48
C0052 MCTRL−Umot
0
{1 V}
800 Motor voltage, function block
MCTRL
l
Read only
l
MCTRL−VACT = 100 % = C0090
^
8.2−25
^
8.2−48
C0053 UG−VOLTAGE
0
{1 V}
900 DC−bus voltage, function block
MCTRL
l
Read only
l
MCTRL−DCVOLT = 100 % =
1000 V
^
8.2−25
^
8.2−48
C0054 IMot
0.0
{0.1 A}
500.0 Current motor current, function
block MCTRL
l
Read only
l
MCTRL−IACT = 100 % = C0022
^
8.2−25
^
8.2−48