Configuration, Overview of monitoring functions – Lenze EVF9333−xV User Manual
Page 348

Configuration
Overview of monitoring functions
8
8.4
l
8.42
EDSVF9333V
EN 6.2−04/2012
Possible responses
l Lenze setting
ü Setting possible
Monitoring
Off
Warning
Message
TRIP
CoDe
Source
Description
Error message
0015
OC5
I x t overload
MCTRL
l
0016
OC6
I
2
x t overload
MCTRL
l
0018
OC8
I
2
x t overload advance warning
MCTRL
C0606
ü
l
ü
x032
LP1
Motor phase failure
(current limit can be set in C0599)
Please note: Can only be used for asynchronous motors. The function block
MLP1 has to be entered in C0465.
MCTRL
C0597
ь
ь
l
x083
Sd3
Interruption of the digital frequency coupling. The input signal ˜Lamp
Control˜ at X9/8 is LOW
Please note: In the case of "Warning" (C0587 = 2), the drive can be
destroyed if the fault is not eliminated in time!
MCTRL
C0587
l
ь
ь
x085
Sd5
At analog input X6/1, X6/2, the input current is < 2 mA
Monitoring only possible if C0034 = 1
MCTRL
C0598
ь
ь
l
0140
ID1
Motor data identifcation − characteristic
MCTRL
l
0141
ID2
Motor data identification − motor data
MCTRL
l
Speed
0200
NMAX
Maximum speed (C0596) has been exceeded.
MCTRL
l
Time−out / overflow
0105
H05
Intern fault (memory)
Internal
l
Parameter setting
0072
PR1
Checksum error in parameter set 1
Internal
l
0073
PR2
Checksum error in parameter set 2
Internal
l
0074
PEr
Program error
Internal
l
0075
PR0
Error in the parameter sets
Internal
l
0077
PR3
Checksum error in parameter set 3
Internal
l
0078
PR4
Checksum error in parameter set 4
Internal
l
0079
PI
Fault during the parameter initialisation
Internal
l
Representation of the error number:
x
0 = TRIP, 1 = message, 2 = warning
E. g. "2091": An external monitoring has triggered EEr warning
1)
Setting only permitted by Lenze service