Configuration – Lenze EVF9333−xV User Manual
Page 316

Configuration
Function blocks
Internal motor control with vector control (MCTRL2)
8.2
8.2.7
l
8.2−54
EDSVF9333V EN 6.2−04/2012
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0140
s
select direct
0
Search direction during flying
restart process
l
Positive direction of rotation:
The motor rotates in CW
direction with view on the
motor shaft
l
Negative direction of rotation:
The motor rotates in CCW
direction with view on the
motor shaft
^
8.2−25
^
8.2−48
0
NSET
Only search in the direction of the
applied setpoint
1
inv. Nset
Only search against the direction
of the applied setpoint
2
pos.
Only search in positive direction of
rotation
3
neg.
Only search in negative direction
of rotation
4
Both, Nset
Search at first in the direction of
the applied setpoint and then
against the direction
5
Both, inv. Nset
Search at first against the
direction and then in the direction
of the applied setpoint
6
Both pos.
Search at first in positive then in
negative direction of rotation
7
Both neg.
Search at first in negative then in
positive direction of rotation
C0142 Start options
1
Starting condition for the flying
restart circuit
^
8.2−36
^
8.2−65
0
Start lock
l
Automatic start is inhibited
after
– mains connection
– Cancel of a message
(t > 0.5 s)
– Trip reset
l
Flying restart circuit is inactive
l
Start after HIGH−LOW−HIGH
level change at X5/28
1
Auto start
Automatic start when
X5/28 = HIGH
l
Flying restart circuit is inactive
2
flying lock
l
Automatic start is inhibited
after
– mains connection
– Cancel of a message
(t > 0.5 s)
– Trip reset
l
Flying restart circuit is active
l
Start after HIGH−LOW−HIGH
level change at X5/28
3
Fly restart
Automatic start when
X5/28 = HIGH
l
Flying restart circuit is active