Configuration – Lenze EVF9333−xV User Manual
Page 320

Configuration
Function blocks
Internal motor control with vector control (MCTRL2)
8.2
8.2.7
l
8.2−58
EDSVF9333V EN 6.2−04/2012
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0913
s
OV handling
0
Value of the motor current during
the flying restart process or after
an OU message
l
When C0913 = 1, the motor is
driven with reduced current to
the setpoint speed during the
flying restart process of after
an OU message.
l
The setting is only effective for
the drives EVF9326 ... EVF9333
^
8.2−25
^
8.2−48
0
inactive
Non−reduced motor current
1
active
Reduced motor current
ƒ The signal at input MCTRL−N−SET is the speed setpoint in [%] and
always refers to the maximum speed (C0011).
ƒ In the most basic configurations, MCTRL−N−SET is connected with the
function block NSET (speed setpoint conditioning).
– It is also possible to connect MCTRL−N−SET with any other analog
output signal of an FB.
ƒ The speed setpoint at MCTRL−N−SET is always limited to ±100 % of the
maximum speed n
max
(C0011).
ƒ The speed setpoint is converted into a frequency setpoint by the motor
control and is limited to a maximum output frequency depending on
the chopper frequency f
chop
.
Chopper frequency f
chop
Maximum output frequency
16 kHz
600Hz
8 kHz
300Hz
2/4 kHz
150Hz
Speed setpoint selection
Speed setpoint limitation