Commissioning, Adjusting the motor entry of motor data – Lenze EVF9333−xV User Manual
Page 190

Commissioning
Adjusting the motor
Entry of motor data
6.6
6.6.1
l
6.6−2
EDSVF9333V EN 6.2−04/2012
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0090
s
Mot voltage
à
0
{1 V}
1000 Rated motor voltage
à
depending on C0086
l
Motor selection in C0086 sets
the corresponding rated motor
voltage in C0090
l
Change of C0090 sets C0086 =
0
^
6.6−1
C0091
s
Mot cos phi
à
0.50
{0.01 }
1.00 Motor cos
j
à
depending on C0086
l
Motor selection in C0086 sets
the corresponding motor cos
j
in C0091
l
Change of C0091 sets
C0086 = 0
^
6.6−1
Choose similar motor
in C0086 according to the
criteria circuit configuration
and rated motor power
Operating mode "87 Hz
delta connection”?
Does C0086 contain
the motor?
Enter motor nameplate data:
C0081 = 3 x P
C0087 = ( 3 - 1) n + n
C0088 = I
C0089 = 87 Hz
C0090 = U
C0091 = cos
r
0
r
r
r
Ц
Ц
j
D
D
Enter motor nameplate data:
C0081, C0087, C0088, C0089,
C0090, C0091
Start entry motor data
Entry motor data completed
Choose motor in C0086
yes
yes
no
no
9300vec096
Fig. 6.6−1
Sequence diagram for motor data entry
P
N
Rated motor power
n
0
Synchronous speed
n
N
Rated motor speed
I
N
D
Rated motor current for delta connection
U
N
D
Rated motor voltage for delta connection
Sequence of the motor data
entry