5 mains choke/mains filter assignment, Mains choke/mains filter assignment, Wiring of the standard device – Lenze EVF9333−xV User Manual
Page 134

Wiring of the standard device
Standard devices in the power range of 55 kW
Mains choke/mains filter assignment
5.6
5.6.5
l
5.6−6
EDSVF9333V EN 6.2−04/2012
Supply conditions
Range
Description
Fuses
l
Only according to UL 248
l
Mains short−circuit current up to 10000 A
rms
: All classes permissible
l
Mains short−circuit current up to 50000 A
rms
: Only classes "J", "T" or "R"
permissible
Cables
l
Only in accordance with UL
l
The cable cross−sections specified in the following apply under the following
conditions:
– Conductor temperature < 60 °C
– Ambient temperature < 40 °C
Observe all national and regional regulations!
9300
Rated fuse current
Cable cross−section
Fuse
L1, L2, L3, PE
Type
[A]
[AWG]
Operation with mains choke/mains filter
EVF9330−xV
100
1
EVF9331−xV
125
1/0
5.6.5
Mains choke/mains filter assignment
Operation with rated power (normal operation)
9300
Mains choke
Interference voltage category according to EN 61800−3 and motor cable length
Component
Component
Type
C2
max. [m]
C1
max. [m]
EVF9330−xV
ELN3−0038H085
EZN3A0037H090
25
E82ZN45334B230
10
E82ZN45334B230
50
EZN3B0037H090
50
EVF9331−xV
ELN3−0027H105−001
EZN3A0030H110
25
E82ZN55334B230
10
EZN3A0030H110N001
3)
25
E82ZN55334B230
50
EZN3B0030H110
50
3)
For controllers with thermal separation
Operation with increased rated power
9300
Mains choke
Interference voltage category according to EN 61800−3 and motor cable length
Component
Component
Type
C2
max. [m]
C1
max. [m]
EVF9330−xV
ELN3−0027H105−001
EZN3A0030H110
25
E82ZN55334B230
10
EZN3B0030H110N001
3)
25
E82ZN55334B230
50
EZN3B0030H110
50
EVF9331−xV
ELN3−0027H105−001
EZN3A0030H110
25
EZN3B0030H110
50
EZN3A0030H110N001
3)
25
3)
For controllers with thermal separation
Installation to UL
Operation at rated power