1 reset of the compensator, Caution – Lenze 8615E User Manual
Page 118

To activate the
compensator the threshold which is to be
set
C94
must
be decreased so that the dancer-Position
controller
be activated. With the setting of Cl 94 = 100 %
(factory setting) the
compensator is disconnected from
the dancer-Position controller.
9.10.1 Reset of the
compensator
The
compensator
be reset (e.g. after finishing the
winding process) via a freely assignable digital input, the operating
unit, or the LECOM
Select the freely assignable terminal which is to be assigned to the
function “diameter compensator reset” via
Cl 12. This function
is assigned to the freely assignable terminal
Cl 13. If
the
compensator is enabled via the freely assignable
terminal, the thresholds will be compared first. When activating the
“diameter compensator reset”, the counter value is set to
After
mains connection, the
compensator is set to
Caution!
If the controller is enabled when the
compensator is reset,
then the counter value is set to zero immediately. Thus, with a high
compensator
when activating the “diameter
compensator reset” the
value which is
of the
abruptly and as a result the field frequency is also
This may lead to high accelerations and the
limiting function
may be activated.
The integration time
be set
Cl 95 (unit [s]), and the
decrement time
be determined
Cl96 (unit
If the output of the dancer-Position controller falls below the
threshold set
Cl 94 after the
compensator has
already been activated, the correction value of the
compensator will not be
as long as
l
the
compensator is reset via a freely assignable
terminal or
l
the supply voltage of the frequency controller is switched off
(e.g. the controller is not connected to the mains) or
l
the
compensator has to be activated again
the output of the dancer-Position controller exceeds the
threshold set
Cl 94.
The function Cl 94 is not reset by controller inhibit.
The threshold set
Cl 94 refers to 100% of the modulation of
the dancer-Position controller.
INFO: 100 % = Diameter compensator swtiched off.
The thresholds for positive and negative
116