7overload, 1 overload protection of the frequency monitoring), 2 overload protection of the motor – Lenze 8615E User Manual
Page 101

7
Overload
7.1
Overload protection of the frequency
monitoring)
The frequency
have an output current monitoring to
them against overload. You
adapt this protection to the
maximum ambient temperature to be expected. The lower the
max.
ambient temperature, the
the limit of the permissible
continuous output current. The permissible continuous output
powes rises the same way.
Cl 19 and Cl20 you
enter
three settings:
l
Rated power up to a maximum of 50°C
l
Increased power up to a maximum of 45°C
l
Maximum power up to a maximum of 40°C
be activated
when using the units 8605, 8607, 8611, 8615)
the output current exceeds the set limit, a fault is indicated after
30 to 60 seconds (see page 148).
7.2
Overload protection of the motor
For motor protection, you
use the
PTC input
terminals 11, 12).
You
use the input to connect a PTC thermistor or a thermal
contact. The motor monitoring is already activated by connecting
the monitoring circuit of the motor to terminals 11 and 12 (remove
wire bridge).
If the motor is overheated, you
the monitoring of the
PTC input such that
l
no
is released
l
TRIP is activated, see page 148
l
a warning is indicated, see page 150
Select the TRIP set-input by
Cl 19 =
and
the
via
(see page 82).
Code
Name
Parameter (Factoty setting printed in
bold)
Acceptance
Digital input
TRIP-Set
SH + PRG
Monitoring
PTC
input
Output power monitoring)