3.1.1.
Simatic-S5
Lenze controllers comply with the standard of PROFIBUS-DP
participants. For communication with Simatic-S5, the following hardware
and software components are necessary:
• S5 interface module IM308-B as from version 5.
• Programming software COM ET200 as from version 4.0
3.1.1.1.
COM-ET200 settings
In the following, specific settings for Lenze controllers are listed when
using the COM-ET 200 program package.
Menu: ET200 system parameters
Bus profile:
DP standard
Menu: Configuration
Station type:
Lenze 2130 Vxx
For this setting, copy the file LE0082TD.200 from
the diskette to the COM-ET200 directory.
Configuration:
User data with DP parameter setting channel
(controller parameter L-C1905 = 1; factory
setting)
0. = 183; 1. = 163; 2. = 147
User data without DP parameter setting channel
0. = 163; 1. = 147
3.1.1.2.
Example program
For easier commissioning, an example program in STEP5 is
provided on the attached diskette (file: 2130@@ST.S5D). The
following function modules (FB) are included:
FB182:
Process data communication. Simplified control of
the controller. The standard functions of the Lenze
controller are mapped to the DRIVECOM profile.
FB183
Parameter data communication. Support of the DP
parameter setting channel. All DRIVECOM and
Lenze parameters can be read and written.