3.1. PROFIBUS-DP operating mode
In the following only the settings for pure PROFIBUS-DP operation are
explained.
Settings for the master
Most of the controller manufacturers demand a controller description
file (controller master data file). Therefore, the following files are saved
in the DOS format on the attached diskette:
File name
Meaning
L_AR0082.GSD
Controller master data file according to
DIN E 19245 part 3
LE0082TD.200
Controller master data file (type file) for
Simatic-S5 COM-ET200/IM308-B
The master must be set as follows:
Function
Setting
(depending on the type of master)
Baud rate
500 kBaud (factory setting)
Value as controller parameter
L-C1902 (page 32).
Communication profile
(Bus profile)
PROFIBUS-DP DIN E 19245 part 3
(DP standard)
Value in controller parameter
L-C1901 = 0 (page 32).
Slave station address
(Station number)
126 (factory setting)
Value as controller parameter
L-C1901 (page 32).
DP configuration data (configuration)
with DP parameter setting channel
(L-C1905=1)
(factory setting)
without DP parameter setting channel
(L-C1905=0)
B7
hex
(183
dez
),A3
hex
(163
dez
),
93
hex
(147
dez
)
A3
hex
(163
dez
),93
hex
(147
dez
)
Lenze PNO identification number
0082
hex
DP parameter setting data
10100000
bin
DP user data length
12 byte (with DP parameter setting
channel)
4 byte
(without DP parameter
setting channel)
Setting as controller parameter
L-C1905 (page 32).