4 - 16

IP

N 07

4-

28

9L

Composer Operating Manual

CONCENTRATION TARGET . . . . . The desired concentration of precursor in

terms of mole %. Also used to multiply the
flow read on the CONTROL IN connector to
form the Bulk Flow Target.

PROCESS GAIN . . . . . . . . . . . . . . The numerical value of the Processes’ gain

(change in the concentration (mole %)
divided by the change in the manipulated
variable (volts).

DEAD TIME . . . . . . . . . . . . . . . . . . The numerical value of the processes’

dead time (sec).

TIME CONSTANT . . . . . . . . . . . . . The numerical value of the processes’ time

constant (sec).

RELAY LIMIT . . . . . . . . . . . . . . . . A parameter that defines a tolerance band

around the Concentration Target or Bulk
Flow Target in terms of an absolute
concentration or flow. Works in conjunction
with the @CONCENTRATION relay

FUZZY . . . . . . . . . . . . . . . . . . . . . . If set to yes (Y) the “fuzzy logic” control

loop is activated, otherwise normal PID
control is executed.

CELL TEMPERATURE . . . . . . . . . The parameter that allows the user to set

the transducer’s resonant chamber’s
temperature (°C). Allowable range is 25 to
65 °C.

CARRIER MW . . . . . . . . . . . . . . . . The parameter representing the molecular

weight of the lighter (or carrier) gas.
Allowable range
is 1 - 1000.

CARRIER

γ

. . . . . . . . . . . . . . . . . . The parameter representing the specific

heat ratio of the lighter (or carrier) gas.

PRECURSOR MW . . . . . . . . . . . . . The parameter representing the molecular

weight of the heavier (or precursor) gas.
Allowable range is 1-1000.0.

PRECURSOR

γ

. . . . . . . . . . . . . . . The parameter representing the specific

heat ratio of the heavier (or precursor) gas.

MFC RANGE BUBBLER . . . . . . . . The parameter representing the full flow

range of the mass flow controller that
regulates the flow through the bubbler
(sccm).