CR10X OVERVIEW

OV-18

SAMPLE PROGRAM 2

Instruction #

Parameter

(Loc:Entry)

(Par#:Entry)

Description

∗1

Enter Program Table 1

01:60

60 second (1 minute) execution interval

Key

#

D

until

01:P00

Erase previous Program before

is displayed

continuing.

01:P17

Measure internal temperature

01:1

Store temp in Location 1

02:P14

Measure thermocouple temperature

(differential)

01:1

1 repetition

02:1

Range code (2.5 mV, slow)

03:5

Input channel of TC

04:1

TC type: copper-constantan

05:1

Reference temp is stored in Location 1

06:2

Store TC temp in Location 2

07:1

Multiplier of 1

08:0

No offset

03:P92

If Time instruction

01:0

0 minutes into the interval

02:60

60 minute interval

03:10

Set Output Flag 0

The CR10X is programmed to measure the thermocouple temperature every sixty seconds.
The If Time instruction sets the Output Flag at the beginning of every hour. Next, the Output
Instructions for time and average are added.

Instruction #

Parameter

(Loc.:Entry)

(Par.#:Entry)

Description

04:P77

Output Time instruction

01:110

Store Julian day, hour, and minute

05:P71

Average instruction

01:1

one repetition

02:2

Location 2 - source of TC temps. to be
averaged

06:P92

If Time instruction

01:0

0 minutes into the interval

02:1440

1440 minute interval (24 hrs.)

03:10

Set Output Flag 0

07: P77

Output Time instruction

01:100

Store Julian day

08: P73

Maximize instruction

01:1

One repetition

02:10

Output time of daily maximum in hours and minutes

03:2

Data source is Input Storage Location 2.