SECTION 14. INSTALLATION AND MAINTENANCE

14-4

TABLE 14.3-1. Typical Alkaline Battery

Service and Temperature

Temperature (°C)

% of 20°C Service

20 - 50

100

15

98

10

94

5

90

0

86

-10

70

-20

50

-30

30

NOTE: This data is based on one "D" cell
under conditions of 50 mA current drain
with a 30 ohm load. As the current drain
decreases, the percent service improves for
a given temperature.

14.3.2 PS12LA LEAD ACID POWER SUPPLY

The PS12LA power supply includes a 12 V, 7.0
amp-hour lead acid battery, a AC transformer
(18 V), and a temperature compensated
charging circuit with a charge indicating diode.
An AC transformer or solar panel should be
connected to the PS12 at all times. The
charging source powers the CR10X while float
charging the lead acid batteries. The internal
lead acid battery powers the datalogger if the
charging source is interrupted. The PS12LA
specifications are given in Table 14.3-2.

The two leads from the charging source can be
inserted into either of the CHG ports, polarity
doesn't matter. A transzorb provides transient
protection to the charging circuit. A sustained
input voltage in excess of 40 V will cause the
transzorb to limit voltage.

Some solar panels are supplied with a
connector, this connector must clipped off so
the two wires can be inserted into the two
terminal ports. It is recommended that these
two leads be stripped and tinned.

The red light (LED) on the PS12LA is on when a
charging source is connected to the PS12LA
CHG ports. The switch turns power on and off
to the 12 V ports, battery charging still occurs
when the switch is off.

CAUTION: Switch the power to "off" before
disconnecting or connecting the power
leads to the Wiring Panel. The Wiring
Panel and PS12LA are at power ground. If
12 V is shorted to either of these, excessive
current will be drawn until the thermal fuse
opens.

INT

EXT

BATT

CHG

OFF

ON

CHG

CHG

+12

+12

1012

INT

EXT

BATT

CHG

O

F

F

O

N

CHG

CHG

CHG

Y

UASA

BATTERY

Y U A S A

NP7 - 12 12

*

CHARGING IN

STRUCTION

(AT 2000

)

SERIAL I/O

CR10X

MEASUREMENT AND CONTROL MODULE

firmware 1983, 1986, 1995

S/N: X 1012

C

CR10X WIRING PANEL

MADE IN U

SA

WIRING

PANEL

NO.

G 12V

POWER

IN

EARTH

CROUND

SE
DEF

G G

H

L AG

H

L AG E3

AG G

G

L AG

H

4

7

8

5

9

10

6

11

12

AG G

G

G

SW 12V CTRL

SW 12V

G

SE
DEF

G G

H

L AG

H

L AG E3

AG

L AG

H

1

1

2

2

3

4

3

5

6

G G H

L AG H

L AG E3 12V

12V

L AG H

SDM

LOGAN, U

TAH

WARNING

:

MADE IN U

SA

WITH 12V C

HARGING

REGULATO

R

PS12 POWER SUPPLY

Logan, Utah

PERMANEN

T DAMAG

E TO RECH

ARGEABLE

CELLS

MAY RESU

LT IF DISCARG

ED

BELO

W 10.5 VOLTS

FUNCT

ION

INT

EXT

BAT

CHG

OFF

ON

CHG
CHG

+12
+12

PS12 BATTERY

EXTERNAL BATTERY

- DO NOT USE W

ITH

INTERNAL

RECHARGEABLE

BATTERY

POWER TO +12 TERM

INALS

INPUT FROM CHARGER OR SOLAR PANEL
16-26 VDC OR AC RMS: POSIT

IVE TO

EITHER

TERMINAL, NEGATIVE

TO OTHER

POWER TO DATALOGGER OR
12V PERIPHERALS

FIGURE 14.3-2 PS12LA

The external port, labeled EXT, is not meant to
be used with the PS12LA unless the internal
battery is removed. The primary power source
is the charging source, and the secondary
power source is the internal lead acid battery.
Connecting a lead acid battery to the external