APPENDIX B. CONTROL PORT SERIAL I/O INSTRUCTION 15

B-13

02:

P89

If X<=>F

START: Limit testing

01:

1

X Loc AIR, mb

02:

3

>=

If reading is

>

1300 mb

03:

1300

F

04:

11

Set high Flag 1

then set Flag 1

high

03:

P89

If X<=>F

01:

1

X Loc AIR, mb

02:

4

<

If reading is < 800 mb

03:

800

F

04:

11

Set high Flag 1

then set Flag 1

04:

P91

If Flag/Port

If Flag

1 is set,

01:

11

Do if flag 1 is high

02:

30

Then Do

do the following.

05:

P86

Do

Output time of failure

01:

10

Set high Flag 0 (output)

06:

P77

Real Time

01:

110

Day,Hour-Minute

07:

P70

Sample

Output out of range reading

01:

1

Rep

02:

1

Loc AIR, mb

08:

P86

Do

Set Intermediate Processing

01:

19

Set high Flag 9

Disable Flag

09:

P86

Do

Set Flag 1 low

01:

21

Set low Flag 1

10:

P95

End

End of If Flag Then Do

11:

P92

If time is

Output mb twice/day

01:

0

minutes into a

02:

720

minute interval

03:

10

Set high Flag 0 (output)

12:

P77

Real Time

01:

110

Day,Hour-Minute

13:

P71

Average

01:

1

Reps

02:

1

Loc AIR, mb

14:

P

End Table 1

Input Location Labels:
1:AIR, mb