Ov3. communicating with cr10x, Ov3.1 cr10x keyboard/display, Ov3.1.1 functional modes – Campbell Scientific CR10X Measurement and Control System User Manual
Page 22: Ov3.1.2 key definition

CR10X OVERVIEW
OV-10
OV3. COMMUNICATING WITH CR10X
An external device must be connected to the
CR10X's Serial I/O port to communicate with
the CR10X. This may be either Campbell
Scientific's CR10KD Keyboard Display or a
computer/terminal.
The CR10KD is powered by the CR10X and
connects directly to the serial port via the SC12
cable (supplied with the CR10KD). No
interfacing software is required.
Computer communication and program editing
is accomplished using Campbell Scientific's
PC208 Datalogger Support Software. This
package contains a program editor (EDLOG),
datalogger communications, automated
telecommunications data retrieval, a data
reduction program, and programs to retrieve
data from Campbell Scientific Storage Modules.
To participate in the programming examples
(Section OV5) you must communicate with the
CR10X. Read Section OV3.1 if the CR10KD is
being used or Section OV3.2 if the PC208
software is being used.
OV3.1 CR10X KEYBOARD/DISPLAY
The SC12 cable (supplied with the CR10KD) is
used to connect the Keyboard/Display to the 9
pin Serial I/O port on the CR10X.
If the Keyboard/Display is connected to the
CR10X prior to being powered up, the "HELLO"
message is displayed while the CR10X checks
memory. The total size of memory is then
displayed (256 for 256 K bytes of memory).
When the CR10KD is plugged in after the
CR10X has powered up, the display is
meaningless until "
∗" is pressed to enter a
mode.
This manual describes direct interaction with
the CR10X. If you have a CR10KD, work
through the direct programming examples in
this overview in addition to using EDLOG and
you will have the basics of CR10X operation as
well as an appreciation for the help provided by
the software.
OV3.1.1 FUNCTIONAL MODES
CR10X/User interaction is broken into different
functional MODES (e.g., programming the
measurements and output, setting time,
manually initiating a block data transfer to
Storage Module, etc.). The modes are referred
to as Star (
∗) Modes since they are accessed by
first keying
∗, then the mode number or letter.
Table OV3.1-1 lists the CR10X Modes.
TABLE OV3.1-1.
∗∗∗∗ Mode Summary
Key
Mode
∗
0
LOG data and indicate active Tables
∗
1
Program Table 1
∗
2
Program Table 2
∗
3
Program Table 3, subroutines only
∗
4
Parameter Entry Table
∗
5
Display/set real time clock
∗
6
Display/alter Input Storage data,
toggle flags or control ports.
∗
7
Display Final Storage data
∗
8
Final Storage data transfer to peripheral
∗
9
Storage Module commands
∗
A
Memory allocation/reset
∗
B
Signature/status
∗
C
Security
∗
D
Save/load Program
∗
#
Used with TGT1 satellite transmitter
OV3.1.2 KEY DEFINITION
Keys and key sequences have specific
functions when using the CR10KD keyboard or
a computer/terminal in the remote keyboard
state (Section 5). Table OV3.1-2 lists these
functions. In some cases, the exact action of a
key depends on the mode the CR10X is in and
is described with the mode in the manual.