SECTION 8. PROCESSING AND PROGRAM CONTROL EXAMPLES

8-10

PROGRAM

*

Table 1 Program

01:

10

Execution Interval (seconds)

;User must toggle Flag 1 to start measurements.
;
01:

If Flag/Port (P91)
1:

21

Do if Flag 1 is Low

2:

0

Go to end of Program Table

;Loop 1, Output every 10 seconds for 10 minutes.
;
02:

Beginning of Loop (P87)
1:

1

Delay

2:

60

Loop Count

03:

Do (P86)
1:

1

Call Subroutine 1

04:

End (P95)

;Loop 2, Output every 30 seconds for 20 minutes.
;
05:

Beginning of Loop (P87)
1:

3

Delay

2:

40

Loop Count

06:

Do (P86)
1:

1

Call Subroutine 1

07:

End (P95)

;Loop 3, Output every 1 minute for 70 minutes.
;
08:

Beginning of Loop (P87)
1:

6

Delay

2:

70

Loop Count

09:

Do (P86)
1:

1

Call Subroutine 1

10:

End (P95)

;Loop 4, Output every 2 minutes for 200 minutes.
;
11:

Beginning of Loop (P87)
1:

12

Delay

2:

100

Loop Count

12:

Do (P86)
1:

1

Call Subroutine 1

13:

End (P95)

;Loop 5, Output every 5 minutes for 700 minutes.
;

14:

Beginning of Loop (P87)
1:

30

Delay

2:

140

Loop Count

15:

Do (P86)
1:

1

Call Subroutine 1

16:

End (P95)

;Loop 6, Output every 10 minutes until stopped
by user.
;
17:

Beginning of Loop (P87)
1:

60

Delay

2:

0

Loop Count

18:

Do (P86)
1:

1

Call Subroutine 1

19:

If Flag/Port (P91)
1:

21

Do if Flag 1 is Low

2:

31

Exit Loop if True

20:

End (P95)

*

Table 3 Subroutines

01:

Beginning of Subroutine (P85)
1:

1

Subroutine 1

02:

Full Bridge (P6)
1:

1

Reps

2:

22

±7.5 mV 60 Hz Rejection Range

3:

1

DIFF Channel

4:

1

Excite all reps w/Exchan 1

5: 1500

mV Excitation

6:

1

Loc [ Level_Ft ]

7:

.46199 Mult

8:

102

Offset

03:

Do (P86)
1:

10

Set Output Flag High

04:

Real Time (P77)
1: 0111

Day,Hour/Minute,Seconds

05:

Sample (P70)
1:

1

Reps

2:

1

Loc [ Level_Ft ]

06:

End (P95)

INPUT LOCATIONS

1 Level_Ft