105 sdi-12 recorder – Campbell Scientific CR10X Measurement and Control System User Manual

Page 152

background image

SECTION 9. INPUT/OUTPUT INSTRUCTIONS

9-20

possible to control a maximum of 256 ports
from the first three datalogger control ports.

For each Rep, the 16 ports of the addressed
SDM-CD16AC are sent according to 16
sequential input locations starting at the input
location specified in parameter 3. Any non-zero
value stored in an input location activates
(connects to ground) the associated SDM-
CD16AC port. A value of zero (0) deactivates
the port (open circuit). For example, assuming 2
Reps and a starting input location of 33,
OUTPUT 1 through 16 of the first SDM-CD16AC
are set according to input locations 33 through
48, and OUTPUT 1 through 16 of the second
SDM-CD16AC are set according to input
locations 49 through 64. See the SDM-CD16AC
manual for detailed instructions and examples.

PARAM.

DATA

NUMBER

TYPE

DESCRIPTION

01:

2

Reps (# of CD16AC
modules sequentially
addressed)

02:

2

Starting SDM Address
(base 4: 00..33)

03:

4

Starting input location

Input locations read: 16 per repetition

*** 105 SDI-12 RECORDER ***

NOTE: Version 1.2 of the SDI-12
specification has been implemented in the
CR10X. Features added in this version are
marked with a dagger (†) and may not be
supported by older SDI-12 sensors.

Instruction 105 allows data to be collected from
SDI-12 sensors. The sensor’s SDI-12 data line
is connected to a control port (C1-C8). The
SDI-12 ground should be connected to a "G"
terminal on the CR10X wiring panel. SDI-12
power may be connected to 12V.

If multiple SDI-12 sensors are used, up to ten
sensors may be connected to a single control
port, but each sensor must have a unique
address and requires a separate Instruction
105.

CAUTION: Instruction 97 with the voice
option and the SDI-12 instructions may not
be in same table. Instruction 97 must be in
Table 1 and the SDI-12 instructions must be
in Table 2.

PARAM.

DATA

NUMBER

TYPE

DESCRIPTION

01:

4

Address (0-9, †10-
126)

02:

2

Command (Table 9-8)

03:

2

Control Port (C1-C8)

04:

4

Input location number

05:

FP

Mult

06:

FP

Offset

Input locations altered: 1-9 (†1-99), depending
on the SDI-12 sensor

Intermediate locations required: 21

PARAMETER 1. ADDRESS

Enter the address of the SDI-12 sensor (0-9).
†Extended addresses (10-126) may be used by
entering the decimal equivalent for the
appropriate ASCII character (see Appendix E).
For example, address ‘A’ would be entered as
65.

PARAMETER 2. COMMAND

Enter a number to select the command to be
sent to the SDI-12 sensor. Usually 0 is entered
to select the M command. The following
Standard SDI-12 commands are supported by
the CR10X:

TABLE 9-8. SDI-12 Command Codes

ENTRY

COMMAND

DESCRIPTION

0

M

Initiate Measurement

0 --

C

†Initiate Concurrent
Measurement

1..9

M1..M9

Additional
Measurement
commands specified
by the SDI-12 sensor

10

V

Initiate Verify
sequence

11

I

Send Identification