SECTION 7. MEASUREMENT PROGRAMMING EXAMPLES

7-23

;Find Temperature and Pressure.
;
04:

Paroscientific (P64)
1:

1

Loc [ Temp_us ]

2:

19

Loc [ Temp_C ]

* Table 3 Subroutines

01:

Beginning of Subroutine (P85)
1:

1

Subroutine 1

02:

Bulk Load (P65)
1:

5.8603

F

2: -3970.3

F

3: -7114.3

F

4:

102.78

F

5:

70.294

F

6:

6.6101

F

7: -119.29

F

8:

30.884

F

9:

3

Loc [ U0 ]

03:

Bulk Load (P65)
1:

0

F

2:

26.337

F

3:

.85170 F

4:

21.801

F

5:

0

F

6:

0

F

7:

1

F

8:

0

F

9:

11

Loc [ D2 ]

04:

End (P95)

End Program

INPUT LOCATION LABELS:

1 Temp_us

12 T1

2 Press_us

13 T2

3 U0

14 T3

4 Y1

15 T4

5 Y2

16 T5

6 Y3

17 Comp_Chk

7 C1

18 plce_hold

8 C2

19 Temp_C

9 C3

20 Press_psi

10 D1

21 Signature

11 D2

7.18 4 TO 20 MA SENSOR USING

CURS100 TERMINAL INPUT
MODULE

A dew point sensor has a 4 to 20 mA output
over the dew point temperature range of -40

° to

+70

°C. The dew point sensor output may be

measured by the CR10X using the CUS100
Terminal Input Module (TIM). The CUS100
uses a 100

Ω, ± 0.01 % resistor to convert the 4

to 20 mA range to 400 to 2000 mV. The
millivolt range was found using the relationship
V = IR, where V is voltage, I is current, and R is
resistance, e.g. the voltage at -40°C is given by
V = 4 mA

∗ 100 Ω = 400 mV. The dew point

sensor is measured with Instruction 2 (Volt Diff).
The multiplier for dew point temperature is
found with the following relationship [70°C -
(-40°C)] / [2000 mV - 400 mV] = 0.06875°C/mV.
The offset is found by taking the linear
relationship °C = mV

∗ Mult + Offset and solving

for the Offset. At -40°C the voltage is 400 mV,
thus the Offset = -40 - [400 mV

0.06875°C/mV] = -67.5°C.

CONNECTIONS
The dew point sensor is measured with a
differential voltage measurement on differential
analog input 4. The CURS100 TIM and dew
point sensor are wired to the CR10X wiring
panel as shown in Figure 7.18-1.

PROGRAM

01:

Volt (Diff) (P2)
1:

1

Reps

2: 25

±2500 mV 60 Hz Rejection
Range

3:

4

DIFF Channel

4:

1

Loc [ Dew_Pnt_C ]

5:

.06875 Mult

6: -67.5

Offset

INPUT LOCATIONS

1 Dew_Pnt_C