B.6.1.4 barometer program – Campbell Scientific CR10X Measurement and Control System User Manual
Page 244

APPENDIX B. CONTROL PORT SERIAL I/O INSTRUCTION 15
B-12
TABLE B-3. Number of Characters/Output and Memory Requirements for Various Barometer
Output Modes
Example: 100 samples are averaged by the
barometer connected to the CR10X via hook-up
#1.
ET = 0.1 * 100 + 0.9
ET = 10.9 seconds
Time out = 10.9/0.01
Time out = 1090
In general, the above equations overestimate
the execution time. When execution speed is
critical, the minimum time out delay must be
determined through trial and error.
B.6.1.4 BAROMETER PROGRAM
The following example program assumes the
barometer is jumpered for TTL output and the
average of one measurement. The following
considerations are accounted for in the
program.
• To preserve the barometer measurement
resolution, barometer data must be output
to the CR10X Final Storage in High
Resolution (OUTPUT PROCESSING
INSTRUCTION 78).
• A communication failure shows up as a
partial value or -99999. It is generally
desirable to exclude this value from any
processing and log the incidence of failure.
A failure may be detected by comparing it to
expected limits. A bad value may be
excluded from processing by temporarily
setting the Intermediate Processing Disable
flag (flag 9). To log a failure the reading
could be output immediately with the time of
occurrence.
01:
P15
Control Port Serial I/O
01:
1
Repetitions
02:
00
Configuration code
ASCII;TTL
03:
0
CTS/Delay before send
04:
1
C1 RTS/DTR
RXD is C2 (code could be 12)
05:
0
Output start location
06:
0
Number of locations to send
07:
13
Input termination character
13
=
CR
08:
9
Max characters to receive
09:
100
Delay for CTS/input
Wait 1 sec
for Input
10:
1
First input location
11:
1
Multiplier
barometer jumpered
12:
0
Offset
for millibar output