SECTION 8. PROCESSING AND PROGRAM CONTROL EXAMPLES

8-4

FIGURE 8.3-1. AM416 Wiring Diagram For Thermocouple and Soil Moisture Block Measurements

PROGRAM

*

Table 1 Program

01:

600.0

Execution Interval (seconds)

01:

Temp (107) (P11)
1:

1

Reps

2:

4

SE Channel

3:

1

Excite all reps w/Exchan 1

4:

1

Loc [ Ref_Temp ]

5:

1

Mult

6:

0

Offset

02:

Do (P86)
1:

41

Set Port 1 High

03:

Beginning of Loop (P87)
1:

0

Delay

2:

16

Loop Count

04:

Do (P86)
1:

72

Pulse Port 2

05:

Excitation with Delay (P22)
1:

1

Ex Channel

2:

0

Delay W/Ex (units = 0.01
sec)

3:

1

Delay After Ex (units =
0.01 sec)

4:

0

mV Excitation

06:

Thermocouple Temp (DIFF) (P14)
1:

1

Reps

2:

21

±2.5 mV 60 Hz Rejection
Range

3:

1

DIFF Channel

4:

1

Type T (Copper-Constantan)

5:

1

Ref Temp Loc
[ Ref_Temp ]

6:

2--

Loc [ TC_#1 ]

7:

1

Mult

8:

0

Offset

07:

AC Half Bridge (P5)
1:

1

Reps

2:

14

±250 mV Fast Range

3:

3

SE Channel

4:

1

Ex Channel Option

5:

250

mV Excitation

6:

18--

Loc [ Soil_#1 ]

7:

1

Mult

8:

0

Offset

08:

End (P95)

09:

Do (P86)
1:

51

Set Port 1 Low

10:

BR Transform Rf[X/(1-X)] (P59)
1:

16

Reps

2:

18

Loc [ Soil_#1 ]

3:

.1

Multiplier (Rf)

11:

If time is (P92)
1:

0

Minutes (Seconds --) into a

2:

60

Interval (same units as above)

3:

10

Set Output Flag High

12:

Real Time (P77)
1: 0110

Day,Hour/Minute

13:

Average (P71)
1:

33

Reps

2:

1

Loc [ Ref_Temp ]