# 958

Figure 6.17 – Configured Produced Exchange 2 - Node 2



4.
Now that Exchange 2 has been configured as a Produced Exchange for Node 2, it is time to

configure Exchange 1 as a Consumed Exchange for Node 2. To do this, first select the
Consumed Exchanges tab (Figure 6.2 [page 33]) and click on the Add Exch button to
create a Consumed Exchange. Then fill in the parameters, as shown in Figure 6.18 below,
and click OK.

In this example, Node 2 will be the only Consumer to receive Exchange 1 from Node 1, and
will not be a member of a Group of Consumers. Also, the Update Timeout is set to 210, which
means Node 2 will expect to receive Exchange 1 from Node 1 at least every 210 mS. Note
this is twice the time, plus 10 mS, that Node 1 was configured to transmit Exchange 1, as
recommended in Table 6.1.