3 egd configuration, Egd configuration – Horner APG XL4 OCS HE-ETN300 User Manual
Page 32
CH.6
SUP0740-07
11/30/2009
Page 32 of 98
# 958
6.3 EGD
Configuration
If EGD protocol will be used in the application, EGD Configuration must be performed, in addition
to the general Ethernet Module Configuration previously described in Chapter 3. To configure
EGD protocol, use Cscape Programming Software to perform the following six steps:
1. Open the Ethernet Module Configuration dialog (Figure 3.5 [page 18]) as described in
Chapter 3.
2. Enable EGD by checking the EGD (Ethernet Global Data) checkbox in the Module
Configuration dialog (Figure 3.5).
3. Click on the Config button next to the EGD (Ethernet Global Data) checkbox to open the
Ethernet Global Data Configuration dialog (Figure 6.1 or Figure 6.2).
Note: The Ethernet Global Data Configuration dialog allows EGD Produced and Consumed
Exchanges to be configured. To configure Produced Exchanges, select the Produced
Exchanges tab (Figure 6.1); to configure Consumed Exchanges, select the Consumed
Exchanges tab (Figure 6.2)
Figure 6.1– Ethernet Global Data (EGD) Configuration Dialog – Produced Exchange Tab
Selected