beautypg.com

Horner APG XL4 OCS HE-ETN300 User Manual

Page 38

background image

CH.6

SUP0740-07

11/30/2009

Page 38 of 98

# 958

1. In the Ethernet Global Data Configuration dialog (Figure 6.2), click on the Add Exch button to

open the Add / Edit Consumed Exchange dialog (Figure 6.5).

Figure 6.5– Add / Edit Consumed Exchange Dialog


2. Configure the Consumed Exchange parameters as follows:

Exchange Number: Enter a number between 1 and 16,383, which will be used to identify
the Exchange to be received.

Producer IP Address: Enter the IP Address of the Producer to receive the Exchange from.

Use Group ID: Check this box to receive an Exchange sent by a Producer to a Group ID.

Group ID:
If the Use Group ID box is checked, enter a number from 1 to 32 in the edit box,
to identify which of the 32 possible Groups of Consumers to become a member of.

Update Timeout: Enter a number (in milliseconds) for how long to wait to receive the
Exchange, before considering it to be late. Typically, this should be set to twice the
corresponding Production Timeout, plus 10 milliseconds.


3. Click OK to accept the new Consumed Exchange configuration, which will be now be

displayed in the upper window of the Ethernet Global Data Configuration dialog (Figure 6.2).


4. To add another Consumed Exchange to the list, click on the Add Exch button again.

5. To edit or delete a Consumed Exchange, highlight it in the upper window of the Ethernet

Global Data Configuration dialog (Figure 6.2), and then click on the Edit Exch or Delete
Exch
button.


6. To quickly change the Producer IP Address in multiple Consumed Exchanges, click on the

Replace Addr button. This will open a dialog to allow the user to search and replace the
Producer IP Address parameter, in all Consumed Exchanges simultaneously.

This manual is related to the following products: