beautypg.com

Allen-bradley 1336-series ac drives, Installation/wiring, Input power conditioning – Alliance Laundry Systems 160 User Manual

Page 86: Caution

background image

© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT

F232120

84

Allen-Bradley 1336-Series AC Drives

Allen-Bradley 1336-Series AC Drives

Installation/Wiring

Input Power Conditioning

The drive is suitable for direct connection to input
power within the rated voltage of the drive. Listed in
Table 46

are certain input power conditions which may

cause component damage or reduction in product life.
If any of the conditions exist, as described in Table 46,

install one of the devices listed under the heading
Corrective Action on the line side of the drive.

IMPORTANT: Only one device per branch circuit
is required. It should be mounted closest to the
branch and sized to handle the total current of the
branch circuit.

An incorrectly installed system can result in
component damage or reduction in product
life. The most common causes are:

1. Wiring AC line to drive output or control
terminals.

2. EXTERNAL voltage application to control
terminals.

3. Incorrect or inadequate AC supply.

Contact factory for assistance with
application or wiring.

W660

CAUTION

Input Power Condition

Corrective Action

Low Line impedance (less than 1% line reactance)

Install Line Reactor

or Isolation Transformer

or Bus Inductor – 5.5 & 11kW (7.5 & 15 HP) drives
only

Greater than 120 kVA supply transformer

Line has power factor correction capacitors

Install Line Reactor

or Isolation Transformer

Line has frequent power interruptions

Line has intermittent noise spikes in excess of 6000V
(lightning)

Phase to ground voltage exceeds 125% of normal line to line
voltage

Remove MOV jumper to ground.

or Install Isolation Transformer with grounded
secondary
if necessary

Ungrounded distribution system

240V open delta configuration (stinger leg)

(1)

Install Line Reactor

(1)

For drives applied on an open delta with a middle phase grounded neutral system, the phase opposite the phase that is tapped in the

middle to the neutral or earth is referred to as the “stinger leg,” “high leg,” “red leg,” etc. This leg should be identified throughout the
system with red or orange tape on the wire at each connection point. The stinger leg should be connected to the center Phase B on the
reactor.

Table 46

This manual is related to the following products: