Alliance Laundry Systems 160 User Manual
Page 62

Allen-Bradley 160-Series AC Drives
F232120
60
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Table 34
Table 34 (continued)
Allen-Bradley Drive Fault Codes (continued)
Fault
Description
Corrective Action
Remarks
39
Phase V Fault
Phase to ground fault detected
between controller and motor in
Phase V.
Check wiring between the drive and motor. Check for
grounded phase.
40
Phase W Fault
Phase to ground fault detected
between controller and motor in
Phase W.
Check wiring between the drive and motor. Check for
grounded phase.
41
UV Short Fault
Excessive current has been
detected between two controller
output terminals.
Check motor and external wiring to the controller output
terminals for shorted condition.
42
UW Short Fault
Excessive current has been
detected between two controller
output terminals.
Check motor and external wiring to the controller output
terminals for shorted condition.
43
VW Short Fault
Excessive current has been
detected between two controller
output terminals.
Check motor and external wiring to the controller output
terminals for shorted condition.
48
Reset to Default Values
Parameters were reset to the
factory default values.
Verify and re-load the desired parameters.