Allen-Bradley 160-Series AC Drives

F232120

60

© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT

Table 34

Table 34 (continued)

Allen-Bradley Drive Fault Codes (continued)

Fault

Description

Corrective Action

Remarks

39

Phase V Fault

Phase to ground fault detected
between controller and motor in
Phase V.

Check wiring between the drive and motor. Check for
grounded phase.

40

Phase W Fault

Phase to ground fault detected
between controller and motor in
Phase W.

Check wiring between the drive and motor. Check for
grounded phase.

41

UV Short Fault

Excessive current has been
detected between two controller
output terminals.

Check motor and external wiring to the controller output
terminals for shorted condition.

42

UW Short Fault

Excessive current has been
detected between two controller
output terminals.

Check motor and external wiring to the controller output
terminals for shorted condition.

43

VW Short Fault

Excessive current has been
detected between two controller
output terminals.

Check motor and external wiring to the controller output
terminals for shorted condition.

48

Reset to Default Values

Parameters were reset to the
factory default values.

Verify and re-load the desired parameters.