PowerFlex 40 and 400 Drive Control Logic
25
F232120
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Table 16 (continued)
PowerFlex 40
Parameter
Group and
Number
PowerFlex 400 Parameter Group
and Number
Parameter
Description
Function
d016
d320
Control
Firmware
Version
Displays the AC drive's firmware
version. For PowerFlex 40 drives, this
will be 70.xx, 80.xx or 90.xx. For
PowerFlex 400 drives, this will be 14.01.
d017
d321
Drive Type
Displays the numeric code of the drive's
rating (e.g., 4508 = 5hp 200V drive)
d018
b012
Elapsed Run
Time
Displays the accumulated time the drive
has output power. The display is in 10-
hour increments (e.g., a display of 1
represents a value of 10 hours).
d019
d319
Testpoint Data
Displays a hexadecimal value of the
“Testpoint Selection” in parameter
A102.
d020
d305
Analog In
(0-10V)
Displays the value (in percentage) of the
voltage at terminal 13(e.g.,
100.0%=10V)
d021
d306
Analog In
(4-20mA)
Displays the value (in percentage) of the
current at terminal 15 (e.g., 0.0%=4mA;
100.0%=20mA)
d022
b010
Output Power
Displays the kilowatts present at
terminals U, V and W (in kW).
d023
d318
Output Power
Factor
Displays the angle in electrical degrees
between the motor voltage and the motor
current.
d024
b014
Drive
Temperature
Displays the present operating
temperature (in Celsius) of the drive's
internal power devices. Refer to Fault
008 in Table 20.
d025
N/A
Counter Status
Not applicable to Alliance Laundry
Systems' equipment. Refer to the manual
supplied with the PowerFlex drive for
detailed information.
d026
N/A
Timer Status
Not applicable to Alliance Laundry
Systems' equipment. Refer to the manual
supplied with the PowerFlex drive for
detailed information.
d028
N/A
Step Logic
Status
Not applicable to Alliance Laundry
Systems' equipment. Refer to the manual
supplied with the PowerFlex drive for
detailed information.