beautypg.com

Power terminal block description – Alliance Laundry Systems 160 User Manual

Page 42

background image

Allen-Bradley 160-Series AC Drives

F232120

40

© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT

Power Terminal Block Description

Input and output power connections are performed
through two separate terminal blocks. Refer to
Figure 23.

Figure 23

A-B 160 Power Block Terminal (TB1, TB2,
GRD)

A-B 160 Torque Specifications

Table 24

L1

R

L2

S

L3

T

BR

-

BR

+

T1

U

T2

V

T3

W

-

DC

+

DC

MOTOR

Ground Tab

Protected AC Input

Terminal Block Two (TB2) -
For Motor

Terminal Block Two (TB2) -
For Motor

Terminal Block One (TB1) -
For Line Power

Protected AC Input

Terminal Block One (TB1) -
For Line Power

FAULT

READY

MOTOR

R/

L1

S/

L2

T/

L3 BR- BR+

U/

T1

V/

T2

W/

T3 DC- DC+

Chassis

Chassis

160 Series C

160 Series A & B

FAULT

READY

R/L1

1 2 3 4 5 6 7 8 9 1011

S/L2 T/L3 BR- BR+

U/T1 V/T2 W/T3DC- DC+

U165ME3A

160 SERIES A & B

160 SERIES C

U165ME3A

Terminals

Description

GRD

Earth Ground

R, S, T (L1, L2, L3)

AC Input Line Terminals

BR+, BR-

Dynamic Brake Resistor
Option – Refer to instructions
with option

DC+, DC-

Capacitor Module Option

U, V, W (T1, T2, T3)

Motor Connection

Table 23

Terminal

Screw

Size

Max/Min Wire

Size mm

2

(AWG)

Max/Min

Torque

N-m (lb-in)

TB1 & TB2
Series A & B

M4

4/0.75

(12/18)

1.81/1.35

(16/12)

4.0 kW
(7.5 HPDP)
Series C

M4

5.26 – 3.31

(10 – 12)

1.35 – 0.90

(12 – 8)

All Other
Ratings
Series C

M4

3.31 – 0.82

(12 – 18)

1.35 – 0.90

(12 – 8)

This manual is related to the following products: