93

Specifications

Electrical and Mechanical Specifications

Specification

FLEXmax 60

FLEXmax 80

Output Current Rating @ 40°C ambient

60 amps continuous

80 amps continuous

Nominal Battery System Voltage

12, 24, 36, 48 or 60 Vdc (adjustable)

PV open circuit voltage

150 Vdc maximum (ETL Rating for UL1741 Standard);
145 Vdc temperature corrected Voc (operational maximum)

Standby power consumption

Less than 1 watt typical

Charge cycle

Three-stage

Voltage regulation set points

13-80 Vdc

Temperature compensation

5 mV per °C per 2 V cell (with optional RTS)

PV input capability

Down convert from any acceptable array voltage to any battery voltage.
Examples: 72 Vdc array to 24 Vdc battery; 60 Vdc array to 48 Vdc battery

Digital Display

4-line, 20-character per line backlit LCD display

Remote Interface

RJ45 modular connector Cat 5 cable 8 wire

Operating Temperature Range*

-40° to 60°C (automaticaly derated above 40°C)

Conduit knockouts

One 1” on the back; one 1” on the left side; two 1” on the bottom

Warranty

Five years parts and labor

Dimensions

13.5” H x 5.75” W x 4” D

16.25” H x 5.75” W x 4”D

Shipping Dimensions

18” H x 11” W x 8” D

21” H x 10.5” W x 9.75”D

Weight

11.6 lb (14 lb boxed)

12.20 lb (15.75 lb boxed)

Options RTS, HUB 4, HUB 10, MATE, MATE2, MATE3

Menu Languages

English and Spanish

Firmware Revision

This manual applies to FLEXmax 80 or FLEXmax 60 charge controllers with a firmware revision of
002.001.xxx or higher.

Regulatory Specifications

Table 3

Regulatory Specifications for All Models

UL 1741 1st Edition; 2005 Version, CSA 107.1-01

CE Conformance European EN 55022 Class B