MATE3 Screens
66
900-0009-01-00 Rev
C
Auxiliary Output (Charge Controller)
This menu controls the output and functionality of the Auxiliary (AUX) output. The charge controller’s
AUX terminals provide a 12 Vdc output that can deliver up to 0.2 Adc to control external loads. Typical
loads include signaling a generator to start, sending a fault alarm signal, or running a fan to cool the
inverter. See page 11 for an image of the AUX terminals. See page 27 for a description of AUX modes.
Figure 66
Auxiliary Output
Aux Modes for the Charge Controller
Aux Modes include nine options with automatic criteria. The options appear in the following order
when the wheel is drawn clockwise. The
Vent Fan
option appears first if the charge controller is set at
factory default values; otherwise, it will tend to display the last option selected. (The options are
described in greater detail beginning on page 29.)
NOTE: The
Remote
option allows the MATE3 to use the AUX output for AGS (see page 41). AGS is
intended for systems with a HUB, inverter, and FLEXmax. If the MATE3 connects only to a FLEXmax,
AGS will only work with DC genset programming. The other AGS functions will not work properly.
Vent Fan
Figure 67
Vent Fan
PV Trigger
Figure 68
PV Trigger
Error Output
Figure 69
Error Output
Set Points:
Enable Voltage
Set Points:
Low Battery Voltage
Set Points:
Enable Voltage
Hold Time
Active: High or Low.
Set Points:
Status
– The
Auxiliary Output status is controlled by the
Aux Mode
–
Selects one of nine options:
Vent Fan, PV
Trigger, Error Output, Night Light, Float, Diversion:Relay,
Diversion:Solid St, Low Battery Disconnect, and Remote.