Operation

38

900-0009-01-00 Rev

C

Figure 26

Setting the Diversion:Solid St Mode (Part 2)

To change the set points for Diversion:Solid St:

1. Press

to advance to the set point screens;

and .

2. Press

to advance to the Time screen. This allows the

user to adjust the minimum time the AUX output is active after
the battery voltage falls below the hysteresis voltage.

3. Press

<-> or <+> to increase or decrease the Hold time values.

4. Press

to increase the Delay time.

5. Press

to return to the Diversion:Solid St TIME and

VOLT screen.

6. Press

to move into the Relative Volts screen.

7. Press

<-> or <+> to increase or decrease the values.

8. Press

to select the hysteresis value.

9. Press

to return to the Diversion:Solid St Time and Volt

screen.

10. From

the

Diversion:Solid St screen, press to return to

the AUX MODE screen.

AUX MODE
Diversion:Solid St
Output: Off Off
EXIT NEXT SET MODE

AUX MODE
Diversion:Solid St

EXIT TIME VOLT

Absorb--Float--EQ
Relative Volts
0.0 00.2
BACK - + HYST

Hold Delay
01.0 Time 00
Seconds
BACK - + DLY+

Hold time shows how long the AUX mode
stays active after the battery voltage has
fallen below the HYST (Hysteresis) set point.
The user can adjust the Hold time from 0.1 to
25 seconds.

The Delay Time shows how long the battery
voltage must be above the Relative Volts
before the AUX mode is activated. It can be
adjusted from 0 to 24 seconds, but is
rarely required
.

Use this screen to establish the set points for
starting and ending the AUX mode relative to the
Absorb, Float, and EQ voltages.

The (hysteresis) set point establishes
when the AUX mode becomes inactive after the
battery voltage falls below the Relative Volts
voltage minus the HYST value.

Continued from previous page…

To Exit:
 Press once to return

to the main menu.

 Press twice to return

to the status screen.