Operation
52
900-0009-01-00 Rev
C
Auto ReStart (Advanced Menu)
This setting allows the user to choose between continuous maximum power point (MPP) tracking, or
occasional restarts of the sweeping process. A restart means the controller abandons the existing
maximum power point value it was using and “re-sweeps”, or begins gathering new power point data.
(See page 95 for more information on MPP tracking.)
Auto ReStart has three options available:
Mode 0 – Initial sweep only and then continuous MPP tracking. Auto ReStart is disabled. The FLEXmax will
continously track the maximum power point without starting over.
Mode 1 – Automatic re-sweep every 90 minutes if controller is in an MPPT mode (MPPT Float, MPPT
Bulk, etc). This will not reset any counters, charging stages, or statistics.
Mode 2 – Automatic re-sweep every 90 minutes if controller is in any charging mode. This will not reset any
counters, charging stages, or statistics.
Figure 45
Auto ReStart
ADVANCED MENU
Auto ReStart
MODE 0
EXIT NEXT MODE
Auto ReStart Screen
To select an Auto ReStart mode:
1.
Navigate to the Auto ReStart screen through the
ADVANCED MENU as instructed in Figure 35.
2. Press
ReStart modes: MODE 0 (default), MODE1, and
MODE2.
ADVANCED MENU
Auto ReStart
Mode 0
EXIT NEXT MODE
ADVANCED MENU
Auto ReStart
MODE 1
EXIT NEXT MODE
ADVANCED MENU
Auto ReStart
MODE 2
EXIT NEXT MODE
To Exit:
Press
Press
Press