Operation, Figure 44 rts compensation – Outback Power Systems FLEXmax 80 Owners Manual User Manual
Page 53
![background image](/manuals/407201/53/background.png)
Operation
900-0009-01-00 Rev
C
51
For example:
During cold weather, a battery often requires a higher charging voltage. Some inverters might not
accommodate these higher voltages and can shut down during charging, cutting off power to their loads.
During hot weather, limiting the RTS Compensation values assures the voltage stays high enough to charge
the batteries instead of dropping too low in reaction to a higher ambient temperature.
Battery manufacturer specifications indicate not to exceed a certain voltage or battery damage could occur.
In all cases, the batteries should be monitored to ensure they are being charged according to the
battery manufacturer’s recommendations.
RTS Compensation has two options available.
WIDE allows the RTS full control over charging. This option uses the default values for the RTS.
LIMIT sets the minimum and maximum voltages for the RTS.
Pressing the soft key below each option switches between the two options. When the LIMIT option is
visible, a
Figure 44
RTS Compensation
ADVANCED MENU
RTS Compensation
A 14.1 V F 13.8 V
EXIT NEXT WIDE
RTS Compensation Screen
To use the default RTS compensation values:
1.
Navigate to the RTS Compensation screen through the
ADVANCED MENU as instructed in Figure 35.
2. If
WIDE is visible above the soft key, the absorb and float values
shown in this screen will be used by the system.
To Exit:
Press
Press
Press
To limit the RTS compensation values:
1.
Navigate to the RTS Compensation screen through the
ADVANCED MENU as instructed in Figure 35.
2. If
WIDE is visible above the soft key, press the
change the display to show LIMIT.
3. Press
Press
< >
until the
is next to the limit to be changed.
The
will switch between the upper and lower limit values
each time it is pressed.
Press
<->
to decrease the value.
Press
<+>
to increase the value.
To Exit:
Press
Press
Press
ADVANCED MENU
RTS Compensation
A 14.1 V F 13.8 V
EXIT NEXT LIMIT SET
RTS COMPENSATION
Upper LIMIT
14.1 V
Upper LIMIT 14.1 V
BACK
- +
ADVANCED MENU
RTS Compensation
A 14.1 V F 13.8 V
EXIT NEXT LIMIT SET
Press
switch back to WIDE.
Press
switch to LIMIT.