Rebulk Voltage (Advanced Menu)
In the Float stage, if the battery voltage falls below the ReBulk Voltage set point for at least
90 seconds, the FLEXmax will automatically initiate a new charge cycle.
Figure 42
Rebulk Voltage
Vbatt Calibration (Advanced Menu)
A quality, calibrated voltmeter will provide even more accurate FLEXmax battery readings if an
undesirable voltage drop occurs. When measuring battery voltage, ensure a good connection is made
to the four wire lugs. Check the battery temperature compensation voltages if the voltages are much
different than expected from the charger setup Absorbing and Float voltage settings.
Figure 43
Vbatt Calibration
RTS Compensation (Advanced Menu)
The RTS Compensation screen allows the user to control the Absorbing and Float voltage limits
during charging when using a Remote Temperature Sensor (RTS). The RTS adjusts charging voltage
depending on battery temperature. (See page 97 for the amount of compensation per degree.)
However, some conditions can make compensation less than optimal, such as extreme weather (hot
or cold), or charging restrictions from the battery manufacturer. Therefore, the RTS Compensation
screen allows the user to control the limits used by the compensation feature.
ADVANCED MENU
Vbatt Calibration
14.1 V 0.0 V
EXIT NEXT - +
Vbatt Calibration
To adjust the set points in the Vbatt Calibration
screen:
1.
Navigate to the Vbatt Calibration screen through
the ADVANCED MENU as instructed in Figure 35.
2. Use
< -> or < + > to increase or decrease the
value. The voltage will change in increments
of 0.1 Vdc.
3. Press
RTS Compensation screen.
To Exit:
Press
Press
Adjusted
Voltage
Adjustment
Value
NOTE: The adjusted voltage value
should appear on the status screen.
ADVANCED MENU
Rebulk Voltage
12.0V
EXIT NEXT - +
Rebulk Voltage
To adjust the set points in the Rebulk Voltage screen:
1.
Navigate to the Rebulk Voltage screen through the
ADVANCED MENU as instructed in Figure 35.
2. Use
< -> or < + > to adjust the voltage limit following the
recommendation of the battery manufacturer. The default
values are 12.0 V, 24.0 V, 36.0 V, 48.0V and 60.0 V.