Low Battery Disconnect (AUX Mode)

This mode disconnects “auxiliary” loads from the batteries in the event of low voltage. These are
separate from the usual loads. Auxiliary loads are controlled by the AUX output, usually by a larger
relay. When the battery voltage falls below the DISCONNECT VOLTS setting, the AUX loads are
disconnected. When the voltage rises above the RE-CONNECT VOLTS, they will be reconnected.

Any loads not controlled this way, such as an inverter, may continue discharging the battery.

Figure 28

Low Battery Disconnect Mode

To set the mode for Low Battery Disconnect in Aux mode:

1.

From the main menu, press <> or <> to move the

to the

left of the Aux.

2. Press

to open the AUX MODE screen.

3. Press

until the Low Batt Disconnect Mode is displayed in

the AUX MODE screen.

4. Press

to cycle through the mode set points;

ON, OFF, or AUTO.
ON activates the AUX output.
OFF deactivates the AUX output.
AUTO controls the output according to the criteria of the

selected AUX mode.

Charger Aux Light
EQ Misc Advanced
Logging Stats
EXIT

  GO

Main Menu

Charger

Aux

Light

EQ Misc Advanced
Logging Stats

EXIT

  GO

AUX MODE
Low Batt Disconnect
Output: Off Off
EXIT NEXT SET MODE

proceeds to the
next AUX MODE screen.

To change the set points for Low Battery Disconnect:

1. Press

to advance to the set point screens; and .

2. Press

to advance to the Delay Time Sec screen.

3. Press

<-> or <+> to increase or decrease the values.

4. Press

to return to the main Low Batt Disconnect screen.

5. Press

to advance to the DISCONNECT VOLTS screen.

6. Press

<-> or <+> to increase or decrease the values.

7. Press to advance to the RE-CONNECT VOLTS screen.

8. Press

<-> or <+> to increase or decrease the values.

9. Press to return to the DISCONNECT VOLTS screen.

10. Press

to return to the Low Batt Disconnect screen.

AUX MODE
Low Batt Disconnect
Output: Off Off
EXIT NEXT SET MODE

AUX MODE
Low Batt Disconnect

EXIT TIME VOLT

RE-CONNECT VOLTS
> 14.4

BACK - + DisV

DISCONNECT VOLTS
< 13.6

BACK - + ReCon

This is the time period the FLEXmax waits before either
activating or deactivating the AUX mode when either
the disconnect or reconnect voltages are reached.

When the low voltage occurs, the timer shows the
seconds remaining before disconnecting.

Delay Time Sec
01 Timer
001
BACK - +

To Exit:

 Press once

to return to the
main menu.

 Press twice

to return to the
status screen.