beautypg.com

Operation, Power up screens – Outback Power Systems FLEXmax 80 Owners Manual User Manual

Page 17

background image

900-0009-01-00 Rev

C

15

Operation

Operation of this unit consists of monitoring screens and programming screens. The majority of
programming screens are accessed using the main menu. See page 24.

Power Up Screens

IMPORTANT:

 The default settings of the FLEXmax are for a 12 Vdc battery bank. Change the

setting after powering up if a different battery voltage is used.

 Once set, the FLEXmax retains the nominal voltage setting. Following any type of

shutdown or disconnect, it will return to operation automatically.

 The PV array voltage is automatically detected. The PV array voltage must never

exceed 150 Voc.

 It is recommended to restore the FLEXmax to factory default settings (see page 53)

and reset the nominal voltage any time the system is substantially revised or the
controller is relocated.

The FLEXmax uses power from the battery bank to operate. The battery voltage must be at least
10.5 volts or higher to power up the FLEXmax. When battery power is detected, the FLEXmax will go
through a series of power-up screens.

Figure 9

Powering up the FLEXmax

Select Version offers two types of options. The English (default) or Spanish selections offer
standardized charge settings in two languages. Selecting Australian leaves the menus in English, but
changes the charging parameters. (For details, see Table 6 on page 99.)

OutBack 12V
Power
Systems
Charge Controller - AU

Power Up Screen

Continued on next page...

On Australian
versions only

System Voltage

To power up the charge controller:

1.

Ensure the PV array and battery circuit breakers are OFF.

2.

Turn ON the battery circuit breaker only.
 The FLEXmax will show the system battery voltage in the

upper right corner of the screen. If the screen reads
Low Battery Voltage, please see the Troubleshooting
section on page 91.

 If the Australian version was previously selected, AU will

be displayed in the lower right corner of the screen.

OutBack 12V
Power
Systems
Charge Controller - AU

PASSWORD
CONTRASENA
***150***
ENTRA - + ENTER

PASSWORD

Screen

To change version settings:

While turning on the circuit breaker, press and hold the first
and third soft keys. This brings up the Select Version screen.
Changing the version settings requires entering a password.

NOTE: This process will reset the FLEXmax to its default
settings. It may be necessary to re-enter previous settings.

To change the system password:

1. Press

or when the Select Version screen

appears on power up.
This will open the PASSWORD screen.

2. Press

<–> or <+> to reduce the number from 150 to 141.

3. Press

or to enter the new password.

This manual is related to the following products: