Restart mode, Mate3 screens – Outback Power Systems FLEXmax 80 Owners Manual User Manual
Page 69
![background image](/manuals/407201/69/background.png)
MATE3 Screens
900-0009-01-00 Rev
C
67
Night Light
Figure 70
Night Light
Float
Figure 71
Float
Diversion: Relay and Solid St
Figure 72
Diversion:Relay and Diversion: Solid St
Low Batt Disconnect
Figure 73
Low Batt Disconnect
Remote
Figure 74
Remote
Restart Mode
This item selects between continuous MPPT, or occasional MPPT restarts. (See pages 21 and 52.)
Figure 75
Restart Mode
Set Points:
0 – Continuous MPPT, 1 – Automatic re-sweep every 90 minutes
in MPPT charging,
2 – Automatic re-sweep every 90 minutes in
any mode.
Set Points: None
This mode can also be used for the MATE3’s AGS function. See
pages 41 and 66 for important information on this function.
Set Points : None
Set Points:
Disconnect
Re-Connect
Disconnect Delay
Set Points (NOTE: All items function identically for both Diversion:
Relay and Diversion: Solid St, except for
Active: High or Low):
Active: High or Low. (Not present in Diversion: Solid St)
Relative Voltage
Hysteresis
Hold
Delay
Set Points :
Active: High or Low.
Threshold
Hysteresis Time
ON Time