beautypg.com

Environmental specifications – HP 4000.6000.8000 Enterprise Virtual Arrays User Manual

Page 143

background image

Table 53 EVA 6x00 UPS loading (continued)

% of UPS capacity

Watts

Enclosures

R12000

R5500

R3000

7.9

21.2

35.3

953

2

4.8

12.8

21.4

577

1

Table 54 EVA 4x00 UPS loading

% of UPS capacity

Watts

Enclosures

R3000

R1500

60.6

1637

4

46.6

94.0

1260

3

32.7

65.9

883

2

18.7

37.9

507

1

Environmental specifications

Table 55 Environmental specifications

50° to 95° F (10° to 35° C) - Reduce rating by 1° F for each 1000 ft. altitude (1.8°
C/1,000 m)

Operating temperature

-40° to 150° F (-40° to 66° C)

Shipping temperature

10% to 90% non-condensing

Operating humidity

5% to 90% non-condensing

Shipping humidity

Up to 8,000 ft. (2,400 m)

Altitude

Not to exceed 500,000 particles per cubic foot of air at a size of 0.5 micron or larger

Air quality

Environmental and operating specifications

143