beautypg.com

Power requirements – HP 4000.6000.8000 Enterprise Virtual Arrays User Manual

Page 140

background image

NOTE:

Further testing is required to update the information in Tables 45-47. Once testing is

complete, these tables will be updated in a future release.

Power requirements

The following tables list the wattage and BTU/hour power requirements for the three supported
operating voltages.

NOTE:

Failover amperage can be estimated at approximately 90% of operational amperage

listed.

Table 47 208V Wattage and BTU/Hour

EVA8x00

EVA6x00

EVA4x00

Enclosures

BTU/h

Watts

VA

Amps

BTU/h

Watts

VA

Amps

BTU/h

Watts

VA

Amps

16789

4920

5104

24.5

12

15060

4414

4578

22.0

11

13775

4037

4188

20.1

10

12489

3660

3797

18.3

9

11204

3284

3406

16.4

10965

3214

3334

16.0

8

9919

2907

3015

14.5

9680

2837

2943

14.1

7

8633

2530

2625

12.6

8394

2460

2552

12.3

6

7348

2153

2234

10.7

7109

2083

2161

10.4

5

6063

1777

1843

8.9

5824

1707

1770

8.5

5585

1637

1698

8.2

4

4777

1400

1452

7.0

4538

1330

1380

6.6

4300

1260

1307

6.3

3

3492

1023

1062

5.1

3253

953

989

4.8

3014

883

916

4.4

2

2207

647

671

3.2

1968

577

598

2.9

1729

507

526

2.5

1

Table 48 230V Wattage and BTU/Hour

EVA8x00

EVA6x00

EVA4x00

Enclosures

BTU/h

Watts

VA

Amps

BTU/h

Watts

VA

Amps

BTU/h

Watts

VA

Amps

16345

4790

4969

21.6

12

15060

4414

4578

19.9

11

13775

4037

4188

18.2

10

12489

3660

3797

16.5

9

11204

3284

3406

14.8

10965

3214

3334

14.5

8

9919

2907

3015

13.1

9680

2837

2943

12.8

7

8633

2530

2625

11.4

8394

2460

2552

11.1

6

7348

2153

2234

9.7

7109

2083

2161

9.4

5

6063

1777

1843

8.0

5824

1707

1770

7.7

5585

1637

1698

7.4

4

477

1400

1452

6.3

4538

1330

1380

6.0

4300

1260

1307

5.7

3

3492

1023

1062

4.6

3253

953

989

4.3

3014

883

916

4.0

2

2207

647

671

2.9

1968

577

598

2.6

1729

507

526

2.3

1

140 Non-standard rack specifications