Table 51 UPS operating time limits (continued)

Minutes of operation

Load (percent)

With 2 ERMs

With 1 ERM

With standby battery

R5500

46

24

7

100

60

31

9

80

106

61

19

50

303

169

59

20

R12000

18

11

5

100

24

15

7

80

41

28

14

50

101

69

43

20

Table 52 EVA 8x00 UPS loading

% of UPS capacity

Watts

Enclosures

R12000

R5500

41.0

4920

12

36.8

98.1

4414

11

33.6

89.7

4037

10

30.5

81.3

3660

9

27.4

73.0

3284

8

24.2

64.6

2907

7

21.1

56.2

2530

6

17.9

47.9

2153

5

14.8

39.5

1777

4

11.7

31.1

1400

3

8.5

22.7

1023

2

5.4

14.4

647

1

Table 53 EVA 6x00 UPS loading

% of UPS capacity

Watts

Enclosures

R12000

R5500

R3000

26.8

71.4

3214

8

23.6

63.0

2837

7

20.5

54.6

91.1

2460

6

17.3

46.2

77.2

2083

5

14.2

37.9

63.2

1707

4

11.1

29.5

49.3

1330

3

142

Non-standard rack specifications