Table 36 EVA4x00 power specifications — 208 Volts

2C4D

2C3D

2C2D

2C1D

Specification

1767

1390

1013

638

Total System Wattage

Typical

1

5585

4300

3014

1729

Total System BTU/hour

4.4

3.5

2.6

1.6

Input Current (A) -
Typical per line

220

170

132

98

In Rush Current (A)

7.5

5.9

4.3

2.7

Input Current (A) -
Maximum per line

Failover Mode

1

Typical is described as a system in normal steady state operation. (i.e., both PDUs operating normally, the array
reading/writing to disk drives in a production environment).
This data represents fully populated drive enclosures with 15K RPM disk drives. Other drive types may vary slightly. For
example, if you are using 10K RPM drives, the power specifications will be approximately 20% less than the 15K RPM
drives.

Table 37 EVA4x00 power specifications — 230 Volts

2C4D

2C3D

2C2D

2C1D

Specification

1767

1390

1013

638

Total System
Wattage

Typical

1

5585

4300

3014

1729

Total System
BTU/hour

4.2

3.3

2.4

1.5

Input Current (A) -
Typical per line

244

190

147

104

In Rush Current (A)

7.1

5.5

4.1

2.6

Input Current (A) -
Maximum per line

Failover Mode

1

Typical is described as a system in normal steady state operation. (i.e., both PDUs operating normally, the array
reading/writing to disk drives in a production environment).
This data represents fully populated drive enclosures with 15K RPM disk drives. Other drive types may vary slightly. For
example, if you are using 10K RPM drives, the power specifications will be approximately 20% less than the 15K RPM
drives.

Table 38 EVA6x00 power specifications — 208 Volts

2C8D

2C7D

2C6D

2C5D

2C4D

Specification

3344

2967

2590

2214

1837

Total System
Wattage

Typical

1

11409

10124

8838

7553

6268

Total System
BTU/hour

8.4

7.4

6.5

5.5

4.6

Input Current (A) -
Typical per line

363

321

280

250

220

In Rush Current (A)

14.2

12.6

11.0

9.4

7.8

Input Current (A) -
Maximum per line

Failover Mode

1

Typical is described as a system in normal steady state operation. (i.e., both PDUs operating normally, the array
reading/writing to disk drives in a production environment).

114

Regulatory notices and specifications